AMC16-DETT Base Station DC Energy Meter

● DC rated voltage: 1 channel: -48VDC

● Support 6 DC loop access

● Accuracy:1%In≤I≤10%In error±2.5%; I>10%In error±2%

● RS485(MODBUS-RTU)

● DIN 35 mm; Easy Installation

● for telecom、base station project

● LED display

  • product detail
  • PARAMETER

General

AMC16-DETT Base Station DC Energy Meter for 5G Tower is specially designed for base stations where have sharing requirements, and switch power supply is without the function of sub-user metering.
The meter could measure 6 circuits DC energy, and supply working current to the matched hall sensors. Meanwhile, it can realize zero drift calibration by upper computer software. It has the functions of telemetering, teleindication, teleadjusting, metering at real time, energy quality abnormal alarm, data storage and processing, data interaction.



Characteristic

Rated U and I

Total 200A/5V

Communication

Single Channel RS485 Communication Protocol

Standard or Customized

Display

LED Indicator Display



Wiring



Dimension




Recommend Hall Sensor


Structure


Input DC rated voltage 1 channel: 0-48VDC
DC current

6 channels hall sensors: total 200A/5V, China Telecom, China Mobile, China

Unicom and the 1st channel reserve 50A/5V, 2nd channel reserve 100A/5V

Commercial power monitoring 1 channel: 0-5VDC
Overload capacity

Voltage: 1.2 times continued, 2 times continued 1s;

Current: 1.2 times continued, 10 times continued 1s

Accuracy

(superposition hall sensors)

1%ln≤ l ≤10% ln error±2.5%; l>10%ln error±2%
Measurement resolution Voltage: 0.01V, Current: 0.01A, Power: 0.01kw, Energy: 0.01kwh
Functions Basic function

Monitor device system time, total voltage, total current, power energy, each channel voltage, current, power, energy; LED display, RS485 communication

Metering function

Start current: under rated voltage, when the load current value of the meter doesn't exceed 1% of the max current,the meter start.

Shunt running current: when there is no current in the current circuit of the meter, and 85%-125% of the rated voltage is applied on the voltage circuit, the calculator shall not have more than one digital change.

Alarm function DC under-voltage, DC over-voltage, one power down, module voltage loss, metering branch error, internal program error, clock error, memory failure, AC input power failure.