● Auxiliary Power Supply: DC24V (±25%)
● Maximum Power Consumption: ≤2VA
● Monitored System Rated Voltage: 0-242VAC
● Monitored System Rated Frequency: 45-60Hz
● Fault Locating Maximum Circuit: 6 Channels
● Fault Locating Response Time: <2s
● Communication Mode: CAN
General
Acrel AIL160-6 insulation fault locators use high sensitivity transformers with high precision signal detection circuitry to detect the signals injected into the system by the AIM-M300/SG Medical Intelligent Insulation Monitors,and to accurately locate the circuits where the insulation faults are located. The AIL160-6 Insulation Fault Locator can locate insulation faults in 6 circuits. Insulation fault location can be used in combination with up to 48 circuits for the AIL160 series.
Function
* Insulation fault location in medical IT systems.
* 6 channels with measuring current transformer per AIL160.
* It can cooperate with AIM-M300/SG Medical Intelligent Insulation Monitor to realize the fault location function. The localization results are indicated by the LEDs of the corresponding circuits.
* It adopts CAN bus technology, it can interact data with other devices
Product Selection

Dimension
Typical Connection
Projects
1. Acrel Medical Isolated Power Supply System in Luanda General Hospital, Angola
2. ACREL Hospital Isolated Power Supply Application in Malaysia
Acrel Medical IT System Insulation Monitoring and Fault Location Products Selection Table V1.0
Note:“□”is optional,“—”is not optional,“■”is selection.
|
Medical Single Phase Isolation Transformer |
AITR-3150 |
AITR-5000 |
AITR-6300 |
AITR-8000 |
AITR-10000 |
|
Capacity |
3150VA |
5000VA |
6300VA |
8000VA |
10000VA |
|
|
□ |
□ |
□ |
□ |
□ |
|
Insulation monitor |
AIM-M10 |
AIM-M100 |
AIM-M200 |
|
|
|
Power supply |
|||||
|
AC220±10% |
|
□ |
|
|
|
|
AC85~265V DC100-300V |
□ |
|
|
|
|
|
DC24V |
|
|
□ |
|
|
|
Communication |
|||||
|
RS485 |
□ |
|
|
|
|
|
RS485+RS485 |
|
□ |
|
|
|
|
RS485+CAN |
|
|
□ |
|
|
|
Output |
|||||
|
DO1(over temperature) |
□ |
|
|
|
|
|
DO1(over temperature) DO2(alarm) |
|
|
□ |
|
|
|
DO1(over temperature) DO2(alarm) DO3(programmable)
|
|
□ |
|
|
|
|
1 channel DC24V |
□ |
|
|
|
|
|
Support fault location |
|||||
|
No |
□ |
□ |
|
|
|
|
Yes |
|
|
□ |
|
|
|
Power supply |
ACLP10-24 |
HDR-60-24 |
|
|
|
|
Insulation monitor |
|||||
|
AIM-M100 |
□ |
|
|
|
|
|
AIM-M200 |
|
□ |
|
|
|
|
Alarm indicator |
AID10 |
AID120 |
AID150 |
AID200 |
|
|
Display |
|||||
|
LED |
□ |
□ |
|
|
|
|
LCD |
|
|
□ |
□ |
|
|
Multi-machine display |
|||||
|
No |
□ |
□ |
|
|
|
|
Yes |
|
|
□ |
□ |
|
|
|
|||||
|
Current transformer |
AKH-0.66P26 |
|
|
|
|
|
|
■ |
|
|
|
|
|
Test signal generator |
ASG150 |
|
|
|
|
|
Support fault location |
|
||||
|
No |
— |
|
|
|
|
|
Yes |
■ |
|
|
|
|
|
Fault locator |
AIL150-4 |
AIL150-8 |
|
|
|
|
Support fault location |
|
||||
|
No |
— |
— |
|
|
|
|
Yes |
□ |
□ |
|
|
|
|
Locate number of channels |
|
||||
|
<=4 |
□ |
|
|
|
|
|
>4; <8 |
|
□ |
|
|
|
|
>8 Note 1 |
□ |
□ |
|
|
|
|
Other |
|
|
|
|
|
Note: 1. More than 8 channels can be freely combined, and the maximum support 24 locate channels.
Ordering example
Example 1: Isolation transformer 8kVA; AC220V; Insulation monitoring; Operating room LCD display; DO output programmable,According to the selection table, confirm the model is AITR-8000, AIM-M100, ACLP10-24, AKH-0.66P26, AID150.
Example 2: Isolation transformer 10kVA; Insulation monitoring; Fault location; ICU LCD display; DO output; Locate 12 loops;
According to the selection table, confirm the model is AITR-10000, AIM-M200, HDR-60-24, AKH-0.66P26, AID150, ASG150, AIL150-4, AIL150-8
| Type | AIL150-4 | AIL150-8 | AIL160-6 |
| Functions | Insulation fault location | ||
| Supply voltage | DC 9V-36V | DC 9V-36V | DC 9V-36V |
| Communication | 1 CAN | 1 CAN | 1 CAN |
| Locating channels | 4ch | 8ch (Maximum 24ch) | 6ch (Maximum 48ch) |
| Dimension | 198X123.6X65(mm) | 215X70X56(mm) | |
| Certifications | CE、IEC | CE、IEC | CE、IEC |
| Standard | IEC61557-9 | ||