● Integrate leakage, overload and earth fault protection
● Comprehensive protection functions
● High accuracy energy metering
● Support Modbus-RTU、Modbus-TCP、Profibus-DP Communication
● 2nd~63rd harmonic measurement
● Wired Temperature measurement - PT100、PT1000、NTC; Wireless Temperature measurement - ATE100、ATE200、ATE400
● Suitable for AC 690V and below low-voltage switchgear, distribution panels and feeder circuits.
General
Acrel ALP500 low-voltage protection measurement and control device (hereinafter referred to as low-voltage protection device) is suitable for low-voltage power distribution circuit with rated voltage to AC660V , integrating power monitoring, feeder protection, opening and closing control, communication networking, node temperature measurement, operation and maintenance management and other functions.
It has various protection functions such as inverse time overcurrent, three-stage overcurrent, overpower, zero sequence overcurrent, undervoltage, overvoltage, unbalance (voltage, current), neutral line overcurrent, and leakage current. Different communication modules can be selected to meet the needs of on-site communication.
The product adopts embedded installation and consists of a main body, a transformer and optional functional modules.
Function
1) Dynamically adjusts protection strategy based on cable heating characteristics to prevent overload burnout;
2) Zero-sequence/leakage current protection;
3) Accurately detects grounding faults to prevent electric shock and fire;
4) Temperature-linked protection;
5) Equipped with wired/wireless temperature measurement modules, it monitors busbar and node temperatures in real time, providing automatic over-temperature warnings;
6) Voltage/current imbalance protection;
7) Promptly detects three-phase imbalances to reduce equipment losses.
Dimension

Dimension of current transformer


Dimension of main body & additional functional module
Typical Connection
Application
Additional Function
|
Additional Functions |
Code Name |
Additional Functions |
Code Name |
|
|
2-63rd harmonic voltage and current |
H |
Waveform record |
WR |
|
|
Communication Module (Choose one) |
1*Profibus DPV0 Communication |
CP |
Leakage protection |
L |
|
2*Profibus DPV0 Communication |
2CP |
Metering module |
S |
|
|
Ethernet Communication (Modbus-TCP protocol) |
MCE |
1*4-20mA Analog output |
M1 |
|
|
4G |
4G |
2*4-20mA Analog output |
M2 |
|
|
Lora |
LORA |
Switch module |
MD |
|
Technical Parameter
|
Technical Parameters |
Technical Indicators |
||
| Auxiliary Power | Support AC 85-265V/DC 100-300V, Wide range power input | ||
| Rated Voltage | AC 380V / 660V,50Hz / 60Hz | ||
| Rated Current | 1 (0.5A-6300A) | XXX/1A Transformer with external CT | |
| 5 (0.5A-6300A) | XXX/5A Transformer with external CT | ||
| 25 (6A-25A) | external current transformer | ||
| 100 (25A-100A) | |||
| Accuracy |
Protection
Accuracy |
3-phase Current | 1.0 Class |
| 3-phase Voltage | 0.5 Class | ||
| Power, Electrical Energy | 2.5 Class | ||
|
Measuring
Accuracy |
3-phase Current、Voltage | 0.5 Class | |
| Active Power, Electrical Energy | 0.5 Class | ||
| Reactive Power, Electrical Energy | 1.0 Class | ||
|
Relay Output
Contact Capacity |
Standard configuration 4 channels | Resistive load、AC250V/10A | |
| Optional 3 channels | |||
| Digital Input | Standard configuration 4 channels passive dry junction | Optional active DC110V、DC220V、AC220V input | |
| Optional10 channels passive dry junction | |||
| Communication | Standard configuration | 2*MODBUS RTU Communication | |
| Optional (Choose one) | 1*MODBUS-TCP | ||
| 1*PROFIBUS-DPV0 | |||
| 2*PROFIBUS-DPV0 | |||
| 1*4G Communication | |||
| 1*Lora Communication | |||
| Application Environment | Working Temperature | -10ºC~55ºC | |
| Storage temperature | -25ºC~70ºC | ||
| Relative humidity | ≤95%, No condensation, No corrosive gas | ||
| Altitude | ≤2000m | ||
| Pollution Level | 3 Class | ||
| Protection Grade | Main Body IP54, Additional function modules IP20 | ||
| Installation Type | III Class | ||