● Max 5 channels temperature monitoring
● Wireless transmit, 470Mhz / 433Mhz;
● Wireless transmission distance, 150 meters;
● Fast sampling frequency, 15s;
● CT powered, starting current ≥5A; cable tied installation;
● Widely temperature measuring range, -50℃~+125℃.
● Application: Switchgear, Busbar, Bus duct, Electric contact, Cable joint, Rain main unit and etc
General
ATE210 wireless temperature sensor has been developed in compliance with Specification for Wireless Temperature Measuring equipment, NB/T 42086-2016. It is suitable for 3-35kV indoor switchgears, including built-in switchgears, handcart switchgears, fixed switchgears and loop-net switchgears. It is also suitable for 0.4kV low-voltage switchgears such as fixed switchgears and drawer switchgears.

Specification
Wireless temperature sensor
|
Name |
Shape |
Parameter instruction |
Installation |
|
ATE200 |
35*35*17mm, L=330mm (length*width*high, belt); -50℃~+125℃, accuracy Class ±1℃, battery powered, life ≥5 years; GSFK communication, 10m communication distance for indoor environment. |
Strap binding |
|
|
ATE200P |
|
35*35*17mm, L=330mm (length*width*high, belt); -50℃~+125℃, accuracy Class ±0.5℃, battery powered, life ≥5 years; GSFK communication, 10m communication distance for indoor environment. |
Outdoor strap binding |
|
ATE400 |
25.82*20.42*12.8mm ( length*width*high); -50℃~+125℃, accuracy class ±1℃, CT induction of electricity powered, starting current ≥5 A; GSFK communication, 10m communication distance for indoor environment. |
Alloy sheet fixed and Powered |
|
|
ATE210 |
![]() |
Max 5-channel temperature monitoing;
-50℃~+125℃, accuracy class ±1℃, CT induction of electricity powered, starting current ≥5 A; LoRa wireless communication, 100m communicaiton distance for indoor envrioment. |
Alloy sheet fixed and Powered |
Transceiver
|
ACREL model |
ATC450-C |
ATC600 |
|
Power supply |
DC24V |
AC/DC 110V/220V |
|
Installation |
Din rail 35mm or screw fixed |
Din rail 35mm |
|
Communication |
Modbus RTU RS485 |
Modbus RTU RS485 |
|
Extra function |
No |
Alarm output 2DO |
Typical Connection
|
Wireless Temp. Measurement |
Item |
Value |
|
Communication distance |
LoRa: 100m for indoor enviroment GSFK: 10m for indoor environment |
|
|
Sampling frequency |
ATE200, ATE200P: 25s; ATE400, ATE210: 15s |
|
|
Transmission frequency |
ATE200, ATE200P: 5min; ATE400, ATE210: 15s |
|
|
Power supply |
CT-powered, starting current >5A |
|
|
Installation |
Alloy chip fixing |
|
|
Range of temperature |
-50°C~125°C |
|
|
Accuracy |
ATE200, ATE210, ATE400: 士 1°C ATE200P: 土0.5°C |
|
|
Application |
Joints in high or low voltage switchgears |
|
|
Service life |
>5 years |
|
|
Environmental Requirement |
Operating temperature |
-50°C~125°C |
|
Relative humidity |
W95% |
|
|
Atmospheric pressure |
86kPa~106kPa |