General
AMC series AC ammeter&voltmeter, adopting AC sampling technology, can directly measure current and voltage of three phase grid. It can be used for local display, and connecting industrial control device to form measuring control system.
Specification
Technical parameter | Value | |
Input | Nominal value |
AC voltage: Single phase AC 100V、400V; Three phase AC 100V、400V、
660V(only 72、96, Three phase soecific line voltage)
AC current: AC 1A、5A; DC voltage: 1000V、300V; Direct current: 75mV、10V、0-20mA、4-20mA、5A; Consult special specification in advance |
Overload |
Voltage: 1.2 times continuous, 2 times continuous 1 second; current: 1.2times continuous,10 times continuous 1 second |
|
Frequency |
45Hz~65Hz
|
|
Power
consumption
|
Power consumption of each voltage, current Input circuit is less than 0.5VA | |
Accuracy class | Class 0.5 | |
Function | Display | LED or LCD display |
Communication |
RS485, Modbus-RTU compatible protocol(1 start bit, 8 data bit, 1 stop bit,no parity) Baud Rate 2400/4800/9600/19200 bps |
Front Panel
Dimension & Installation
Wiring
Wiring sample of current and voltage
Typical Connection

Meter type | Basic function | Shape | Optional function |
AMC48-AI
AMC48-AV
|
Current,voltage
measurement;
LED digital display
|
48 Square
|
1、1 channel RS485 communication (/C)
2、1 channel transmitting output (/M)
|
AMC48-AI3
AMC48-AV3
|
NO | ||
AMC48L-AI
AMC48L-AV
|
Current or voltage
measurement;
LCD liquid crystal display
|
1、1 channel RS485 communication (/C)
2、1 channel transmitting output (/M)
|
|
AMC48L-AI3
AMC48L-AV3
|
NO | ||
AMC72-AI
AMC72-AV
AMC72-AI3
AMC72-AV3
|
Current or voltage
measurement;
LED digital display
|
72 Square |
1、1 channel RS485 communication (/C)
2、1 channel transmitting output (/M)
3、1 channel relay alarm(/J)
4、transmitting output+RS485 communication(/MC)
5、RS485 communication+ switching 2DI2DO(/KC)
6、1 channel relay alarm+1 channel transmitting
output+RS485 communication(/JMC)
|
AMC72-DI
AMC72-DV
|
Direct current or Direct
voltage measurement;
LED digital display
|
||
AMC72L-AI
AMC72L-AV
AMC72L-AI3
AMC72L-AV3
|
Current or voltage
measurement;
LCD liquid crystal display
|
||
AMC72L-DI
AMC72L-DV
|
Direct current or Direct
voltage measurement;
LCD liquid crystal display
|
||
AMC96-AI
AMC96-AV
AMC96-AI3
AMC96-AV3
|
Current or voltage
measurement;
LED digital display
|
96 Square |
1、1 channel RS485 communication (/C)
2、transmitting output (/M or /3M)
3、1 channel relay alarm (/J)
4、transmitting output+RS485 communication(/MC or/M3C)
5、RS485 communication+ switching 4DI2DO (/KC)
6、1 channel relay alarm+1 channel transmitting
output+RS485 communication(/JMC)
|
AMC96L-AI
AMC96L-AV
AMC96L-AI3
AMC96L-AV3
|
Current or voltage
measurement;
LCD liquid crystal display
|
Q: No display on power?
A: Check whether the supply voltage is within the operating voltage range.
Q: Incorrect reading of voltage,current,electricty,etc?
A: Checking that the voltage/current ratio setting are correct; Checking whether the wiring mode setting is consistent with the actual situation;
Checking whether the voltage transformer and current transformer are in good condition.
Q: Abnormal communication?
A: Check whether the adress,baud rate,check bits in the communication; Setting are consistent with the host computer;
Check whether the RS485 converter is normal; Check the connection is corrent if the resistor above 120 ohm is connected in parallel at the communication end.