Wireless Temperature Sensors in Beijing Daxing International Airport
Wireless Temperature Sensors in Beijing Daxing International Airport
Wireless Temperature Sensors in Beijing Daxing International Airport
Apr 14, 2021
Share:

Abstract: With the development of the electrical industry, the requirements for the safety and reliability of equipment are getting higher and higher. Under this condition, a wireless temperature measurement system for high-voltage equipment came into being. It is to install temperature sensors with batteries or CT powered at each temperature measurement point. The sensor sends the temperature measurement data to the receiving unit, and the receiver can be connected to the system to realize the electrical temperature monitoring. This article introduces the application of Acrel wireless temperature measurement products in Beijing Daxing International Airport.


Keywords: Wireless Temperature Sensor, Online Temperature Monitoring System, High-voltage Switchgear


1.Project Overview

As a large international transportation hub, Beijing Daxing International Airport is located between Beijing Daxing District and Guangyang District, Langfang City, Hebei Province. The airport terminal high-voltage substation includes 668 high-voltage cabinets. Acrel provided it with a wireless temperature measurement solution. The upper and lower contacts and cable joints of each high-voltage cabinet were tested at 9 points. There were a total of 6015 wireless temperature sensors. At the same time, it should be installed an ASD320 intelligent control device on each high-voltage cabinet.


2.Introduction of Wireless Temperature Measurement Products

Wireless temperature measurement products are suitable for temperature monitoring of cable joints, circuit breaker contacts, copper bars, cables, and equipment surfaces in medium-voltage and low-voltage switchgear, and reflect the operating status of equipment in a timely, continuous and accurate manner to improve the safety on equipment.


3.Introduction of Acrel Wireless Temperature Measurement Solution

3.1 Solution for High-voltage and Low-voltage Switchgear (With display)


3.2 Solution for High-voltage and Low-voltage Switchgear (Without display)


4.Product Selection

4.1 Wireless Temperature Sensor

Model

Product

Technical Parameters

Installation

ATE100M

Battery operated sensor, 32.4*32.4*16mm,

-50~+125℃, Accuracy: ±1℃,

470MHz, 150 meters in an open space

Magnetic

ATE100

Battery operated sensor, 62.4*32.4*16mm,

-50~+125℃, Accuracy: ±1℃,

470MHz, 150 meters in an open space

Screwed

ATE200

Battery operated sensor, 35*35*17mm,

-50~+125℃, Accuracy: ±1℃,

470MHz, 150 meters in an open space

Bundled

ATE100P

Battery operated sensor, 62.4*32.4*16mm,

-50~+150℃, Accuracy: ±0.5℃,

470MHz, 150 meters in an open space, IP68

Screwed (Outdoor)

ATE200P

Battery operated sensor, 35*35*17mm,

-50~+150℃, Accuracy: ±0.5℃,

470MHz, 150 meters in an open space, IP68

Bundled (Outdoor)

ATE400

CT powered sensor, 25.82*20.42*12.8mm,

Current: 5A, three colors,

470MHz, 150 meters in an open space

Fixed by alloy strap


4.2 Receiver and Display Unit

Model

Product

Function

ATC450-C

Power supply: DC 24V,

Installation: 35mm DIN rail/ Screwed,

Dimension: 65*45*28mm,

Communication: RS485(Modbus-RTU),

Receive the data of 60 sensors.

ATC600-C

Power supply: AC/DC 110V/220V,

Installation: 35mm DIN rail,

Communication: RS485(Modbus-RTU),

Alarm: 2DO

Receive the data of 240 sensors.

ARTM-Pn

Power supply: AC85-265V/DC100-300V,

Installation: panel mounted, 92*92mm,

Dimension: 96*96*17mm,

Communication: RS485(Modbus-RTU),

Receive the data of 60 sensors.